ERL PHASE TESLA 4000-SV

Recording for a fully digital substation environment

TESLA 4000 SV supports both IEC 61850-9-2 LE as well as IEC 61869-9 to subscribe to Sampled Value streams from Merging Unit.
It also publishes and subscribes to GOOSE messages from protective relays and switchgear. The Model 4000-SV also supports direct streaming of MMS reports to remote clients, eliminating the need for RTUs.
The Model 4000-SV supports the top-down or bottom-up engineering process defined in the IEC 61850-6 standard which enables standardization and interoperability of fault and disturbance recording solutions as the industry moves towards fully digital substations.

Applications

  • Complete integrated insight of power system health
  • Performance monitoring of substation IEDs and equipment
  • Over 1000 user settable triggers capture vital information that could be missed by relays in the system
  • As a PMU, streams up to 36 phasors, 24 analog quantities, 64 digital statuses, and 256 GOOSE Boolean Virtual Inputs simultaneously

Features and benefits

  • Easy-to-use setting and analysis software
  • GOOSE subscription and publishing on any port
  • IEC 61850 Edition 2 and IEC 61869-9 support
  • Support for PRP network redundancy protocol on multiple ports, up to 3 redundancy pairs
  • Support for GOOSE subscription from different data types including Boolean, Dbpos, Health, Int32
  • Time synchronization is supported via legacy IRIG-B or Precision Time Protocol (PTP); PTP is fully compliant with applicable power and utility industry profiles
  • Circular sequence of events report buffer of 1000 events
  • Sampling rate configurable at 80 or 256 s/c for IEC61850 9-2 stream and 4000, 4800, 14400 Hz for IEC 61869-9 SV stream
  • IEEE C37.118-2014 and IEEE/IEC 60255-118-1:2018 compliant
  • Swing records with a sampling rate of 1 or 2 s/c
  • Different storage capacities available from 64GB, and 1TB

CONFIGURATION SOFTWARE